U.S. flag   An official website of the United States government
Dot gov

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Https

Secure .gov websites use HTTPS
A lock (Dot gov) or https:// means you've safely connected to the .gov website. Share sensitive information only on official, secure websites.

NOTICE UPDATED - April, 25th 2024

NIST has updated the NVD program announcement page with additional information regarding recent concerns and the temporary delays in enrichment efforts.

CVE-2022-38371 Detail

Current Description

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions), APOGEE PXC Compact (P2 Ethernet) (All versions), APOGEE PXC Modular (BACnet) (All versions), APOGEE PXC Modular (P2 Ethernet) (All versions), Desigo PXC00-E.D (All versions >= V2.3), Desigo PXC00-U (All versions >= V2.3), Desigo PXC001-E.D (All versions >= V2.3), Desigo PXC100-E.D (All versions >= V2.3), Desigo PXC12-E.D (All versions >= V2.3), Desigo PXC128-U (All versions >= V2.3), Desigo PXC200-E.D (All versions >= V2.3), Desigo PXC22-E.D (All versions >= V2.3), Desigo PXC22.1-E.D (All versions >= V2.3), Desigo PXC36.1-E.D (All versions >= V2.3), Desigo PXC50-E.D (All versions >= V2.3), Desigo PXC64-U (All versions >= V2.3), Desigo PXM20-E (All versions >= V2.3), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (Versions including affected FTP server), TALON TC Compact (BACnet) (All versions), TALON TC Modular (BACnet) (All versions). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.


View Analysis Description

Severity



CVSS 3.x Severity and Metrics:

NIST CVSS score matches with CNA score
CNA:  Siemens AG
Base Score:  7.5 HIGH
Vector:  CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H


NVD Analysts use publicly available information to associate vector strings and CVSS scores. We also display any CVSS information provided within the CVE List from the CNA.

Note: The NVD and the CNA have provided the same score. When this occurs only the CNA information is displayed, but the Acceptance Level icon for the CNA is given a checkmark to signify NVD concurrence.

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving NIST webspace. We have provided these links to other web sites because they may have information that would be of interest to you. No inferences should be drawn on account of other sites being referenced, or not, from this page. There may be other web sites that are more appropriate for your purpose. NIST does not necessarily endorse the views expressed, or concur with the facts presented on these sites. Further, NIST does not endorse any commercial products that may be mentioned on these sites. Please address comments about this page to nvd@nist.gov.

Hyperlink Resource
https://cert-portal.siemens.com/productcert/pdf/ssa-313313.pdf Patch  Vendor Advisory 
https://cert-portal.siemens.com/productcert/pdf/ssa-935500.pdf Patch  Vendor Advisory 

Weakness Enumeration

CWE-ID CWE Name Source
CWE-401 Missing Release of Memory after Effective Lifetime cwe source acceptance level NIST  
CWE-400 Uncontrolled Resource Consumption Provider acceptance level Siemens AG  

Known Affected Software Configurations Switch to CPE 2.2

CPEs loading, please wait.

Denotes Vulnerable Software
Are we missing a CPE here? Please let us know.

Change History

3 change records found show changes

Quick Info

CVE Dictionary Entry:
CVE-2022-38371
NVD Published Date:
10/11/2022
NVD Last Modified:
02/14/2023
Source:
Siemens AG